AHEB-0808

•  Scalable
•  Supervised Inputs
•  3rd Party Integration
•  I/O Relay Available. 2/ 8/ 16/ etc.
SPECIFICATIONS
General Information AHEB-0808
Primary Power 12 - 24 VDC ± 20%, 550 mA maximum
RS-485 Connectivity Output: RS-485 standard / OSDP V2.2 (Dedicated for AHSC-1000/ AHDU series controller communication)
Input: RS-485 Input standard / OSDP V2.2 (Dedicated for AHEB series IO expansion board communication)
Number of Ports
AHEB-0808 :1*RS-485 8*supervised input (AUX IN) 8*relay output (AUX OUT) 1* power Input (PWR IN) 1*power output (PWR OUT) 1*power detection (AC Fail) 1* backup battery detection (BAT Fail) 1*tamper input (TMPR)
Inputs 4 state supervision, resistor values (5% tolerance), Normally open contact: use 1.2k, 2.2k. 4.7k or 10k/ Normally closed contact: use 1.2k, 2.2k. 4.7k or 10k
Outputs AHEB-0808:8 relays, 8* Form-C with dry contacts
AHSC/ AHDU INTERFACE  
RS-485 Protocol 12 - 24 VDC ± 20%, 550 mA maximum
OSDP Mode 9600-115200 bps, OSDP V2.2, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit.Maximum cable length: 2,000 ft. (609.6m)
Data Inputs OSDP supported.
Maximum cable length: 500 ft. (152m)
CABLE REQUIREMENT  
Power & Relays 12 - 24 VDC ± 20%, 550 mA maximum
RS-485 Port 9600-115200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and1 stop bit.One twisted pair with drain wire and shield, 120 ohm resistance, 22-18 AWG,Maximum cable length: 3937ft (1200m)
MECHANICAL  
Dimensions 7.6” W x 4.6” L x 0.7” H (193 x 116 x 17.5mm)
Weight 5.8oz (165.3g)
Mounting Wall Mount
ENVIRONMENTAL  
Temperature -22°F ~ 158°F (-30°C~70°C), Operating & Storage
Humidity 0-95%RHNC
Certification(s) CE, FCC, RoHS, UL294
Security Rating Data Storage Encrypted with Certified EAL6+ Crypto Chipset
SOFTWARE INTERFACE  
Supported Softwares Armatura One Security System, Cielo365 (coming soon)